Tubo termorretráctil de baja tensión


Add insulation between busbars in medium-voltage substations up to 36 kV. This heat-shrink tubing is intended to reduce required electrical clearance and provides resistance to tracking, corrosion, UV exposure and weathering for insulated busbar applications.
Add insulation between busbars in medium-voltage substations up to 36 kV. This heat-shrink tubing is intended to reduce required electrical clearance and provides resistance to tracking, corrosion, UV exposure and weathering for insulated busbar applications.
Heat Shrink Bus-bar Insulation Tubing
Corresponda su número de artículo con las dimensiones y clasificaciones que se indican a continuación.
| Prueba | Método de prueba | Requisito |
|---|---|---|
| Resistencia a la tracción | ASTM D 2671 | ≥11.8MPa |
| Alargamiento a la rotura | ASTM D 2671 | 700% |
| tensile strength after heat aging | ASTM D 2671/120℃,168小h | ≥10MPa |
| Alargamiento a la rotura tras envejecimiento térmico | ASTM D 2671/120℃,168h | ≥500% |
| Longitudinal shrinkage | ASTM D 2671 | 0 to-10% |
| Electrical strength | IEC 243 | ≥20KV/mm |
| Dielectric constant | IEC 250 | 3.0 Max |
| Resistividad volumétrica | IEC 93 | 10 13 Ω·cm |
| Flame retardancy (oxygen index) | ASTM 4589 | ≥25 |
| Copper corrosive 120 ° C, 168 hours | ASTM D 2671 | Pass |
| Low temperature brittleness -40 ° C, 4 hours | ASTM D 2671 | No crack |
| Water absorption rate | ISO 62/23℃,14 days | ≤0.5% |
Comparta la referencia del producto, la especificación y la cantidad.
Echemos un vistazo más de cerca a sus requisitos.
Búsquedas sugeridas