{"id":1300,"date":"2022-10-10T00:00:00","date_gmt":"2022-10-10T00:00:00","guid":{"rendered":"https:\/\/ylu6kzueag.wpdns.site\/news\/electrical-grounding-specifications-and-requirements\/"},"modified":"2022-10-10T00:00:00","modified_gmt":"2022-10-10T00:00:00","slug":"electrical-grounding-specifications-and-requirements","status":"publish","type":"post","link":"https:\/\/www.yojiuelec.com\/hi\/news\/electrical-grounding-specifications-and-requirements\/","title":{"rendered":"Electrical grounding specifications and requirements"},"content":{"rendered":"<p><strong>What are the specifications and requirements for <a href=\"\/hi\/%e0%a4%85%e0%a4%b0%e0%a5%8d%e0%a4%a5%e0%a4%bf%e0%a4%82%e0%a4%97-%e0%a4%b8%e0%a4%bf%e0%a4%b8%e0%a5%8d%e0%a4%9f%e0%a4%ae\/\">electrical grounding<\/a>?<br \/>\n<\/strong><\/p>\n<p>The protection methods for electrical system configuration include: protective grounding, protective neutral connection, repeated grounding,<\/p>\n<p>working grounding, etc. A good electrical connection between a part of electrical equipment and the earth is called grounding. The metal<\/p>\n<p>conductor or metal conductor group directly contacting with the earth soil is called the grounding body: the metal conductor connecting the<\/p>\n<p>grounding part of the electrical equipment to the grounding body is called the grounding wire; The grounding body and grounding wire are<\/p>\n<p>collectively referred to as grounding devices.<\/p>\n<p>\u00a0<\/p>\n<p><strong>Grounding concept and type<\/strong><\/p>\n<p>(1) Lightning protection grounding: grounding for the purpose of quickly introducing lightning into the earth and preventing lightning damage.<\/p>\n<p>If the lightning protection device shares a general grounding grid with the working grounding of the telegraph equipment, the grounding resistance<\/p>\n<p>shall meet the minimum requirements.<\/p>\n<p>\u00a0<\/p>\n<p>(2) AC working grounding: metal connection between a point in the power system and the earth directly or through special equipment. Working<\/p>\n<p>grounding mainly refers to the grounding of transformer neutral point or neutral line (N line). N wire must be copper core insulated wire. There<\/p>\n<p>are auxiliary equipotential terminals in the power distribution, and the equipotential terminals are generally in the cabinet. It must be noted that<\/p>\n<p>the terminal block cannot be exposed; It shall not be mixed with other grounding systems, such as DC grounding, shielding grounding, anti-static<\/p>\n<p>grounding, etc; It cannot be connected with PE line.<\/p>\n<p>\u00a0<\/p>\n<p>(3) Safety protection grounding: safety protection grounding is to make a good metal connection between the uncharged metal part of electrical<\/p>\n<p>equipment and the grounding body. The electrical equipment in the building and some metal components near the equipment are connected with<\/p>\n<p>PE lines, but it is strictly prohibited to connect the PE lines with N lines.<\/p>\n<p>\u00a0<\/p>\n<p>(4) DC grounding: In order to ensure the accuracy and stability of each electronic equipment, a stable reference potential must be provided in addition<\/p>\n<p>to a stable power supply. The insulated copper core wire with large section area can be used as the lead, one end of which is directly connected with the<\/p>\n<p>reference potential, and the other end is used for DC grounding of electronic equipment.<\/p>\n<p>\u00a0<\/p>\n<p>(5) Anti static grounding: the grounding to prevent the interference of static electricity generated in the dry environment of the computer room in the<\/p>\n<p>intelligent building to electronic equipment is called anti-static grounding.<\/p>\n<p>\u00a0<\/p>\n<p>(6) Shielding grounding: in order to prevent external electromagnetic interference, the shielding wire or metal pipe inside and outside the electronic<\/p>\n<p>equipment enclosure and the equipment are grounded, which is called shielding grounding.<\/p>\n<p>\u00a0<\/p>\n<p>(7) Power grounding system: in electronic equipment, to prevent interference voltage of various frequencies from invading through AC and DC power<\/p>\n<p>lines and affecting the operation of low-level signals, AC and DC filters are installed. The grounding of filters is called power grounding.<\/p>\n<p>\u00a0<\/p>\n<p><strong>The functions of grounding are divided into protective grounding, working grounding and anti-static grounding<\/strong><\/p>\n<p>(1) The metal shells, concrete, poles, etc. of electrical equipment may be electrified due to insulation damage. In order to prevent this situation from<\/p>\n<p>endangering personal safety and avoiding electric shock accidents, the metal shells of electrical equipment are connected with the grounding device<\/p>\n<p>to protect the grounding. When the human body touches the electrical equipment with the shell electrified, the contact resistance of the grounding<\/p>\n<p>body is far less than the human body resistance, Most of the current enters the earth through the grounding body, and only a small part flows through<\/p>\n<p>the human body, which will not endanger human life.<\/p>\n<p>\u00a0<\/p>\n<p>(2) The grounding conducted to ensure the reliable operation of electrical equipment under normal and accident conditions is called working<\/p>\n<p>grounding. For example, the direct grounding and indirect grounding of neutral point as well as the repeated grounding of zero line and lightning<\/p>\n<p>protection grounding are all working grounding. In order to introduce lightning into the ground, connect the grounding terminal of lightning<\/p>\n<p>protection equipment (lightning rod, etc.) to the ground to eliminate the harm of lightning overvoltage to electrical equipment, personal property,<\/p>\n<p>also known as overvoltage protection grounding.<\/p>\n<p>\u00a0<\/p>\n<p>(3) The grounding of fuel oil, natural gas storage tanks, pipelines, electronic equipment, etc. is called anti-static grounding to prevent the impact<\/p>\n<p>of electrostatic hazards.<\/p>\n<p>\u00a0<\/p>\n<p><strong>Requirements for installing grounding device<\/strong><\/p>\n<p>(1) The grounding wire is generally 40mm \u00d7 4mm galvanized flat steel.<\/p>\n<p>(2) The grounding body shall be galvanized steel pipe or angle steel. The diameter of the steel pipe is 50mm, the pipe wall thickness is not less<\/p>\n<p>than 3.5mm, and the length is 2-3 m. 50mm for angle steel \u00d7 50mm \u00d7 5 mm.<\/p>\n<p>(3) The top of the grounding body is 0.5~0.8m away from the ground to avoid thawing soil. The number of steel pipes or angle steels depends<\/p>\n<p>on the soil resistivity around the grounding body, generally not less than two, and the spacing between each is 3~5m<\/p>\n<p>(4) The distance between the grounding body and the building shall be more than 1.5m, and the distance between the grounding body and the<\/p>\n<p>independent lightning rod grounding body shall be more than 3m.<\/p>\n<p>(5) Lap welding shall be used for the connection of grounding wire and grounding body.<\/p>\n<p>\u00a0<\/p>\n<p><strong>Methods for reducing soil resistivity<\/strong><\/p>\n<p>(1) Before the installation of the grounding device, the resistivity of the soil around the grounding body shall be understood. If it is too high,<\/p>\n<p>necessary measures shall be taken to ensure that the grounding resistance value is qualified.<\/p>\n<p>(2) Change the soil structure around the grounding body within 2~3m of the soil around the grounding body, and add substances that are<\/p>\n<p>impermeable to water and have good water absorption, such as charcoal, coke cinder or slag. This method can reduce the soil resistivity to<\/p>\n<p>the original 15~110.<\/p>\n<p>(3) Use salt and charcoal to reduce soil resistivity. Use salt and charcoal to tamp in layers. The charcoal and fine are mixed into a layer, about<\/p>\n<p>10~15cm thick, and then 2~3cm of salt is paved, a total of 5~8 layers. After paving, drive into the grounding body. This method can reduce the<\/p>\n<p>resistivity to the original 13~15. However, salt will be lost with running water over time, and it is generally necessary to replenish it once more<\/p>\n<p>than two years.<\/p>\n<p>(4) The soil resistivity can be reduced to 40% by using long-acting chemical resistance reducer. The grounding resistance of electrical equipment<\/p>\n<p>shall be tested once each year in spring and autumn when there is less rain to ensure that the grounding is qualified. Generally, special<\/p>\n<p>instruments (such as ZC-8 grounding resistance tester) are used for testing, and ammeter voltmeter method can also be used for testing.<\/p>\n<p>\u00a0<\/p>\n<p><strong>The contents of grounding inspection include<\/strong><\/p>\n<p>(1) Whether the connecting bolts are loose or rusted.<\/p>\n<p>(2) Whether the corrosion of grounding wire and grounding body below the ground is desoldered.<\/p>\n<p>(3) Whether the grounding wire on the ground is damaged, broken, corroded, etc. The power line of overhead incoming line, including the neutral<\/p>\n<p>line, shall have a section of no less than 16 mm2 for aluminum wire and no less than 10 mm2 for copper wire.<\/p>\n<p>(4) In order to identify the different uses of various conductors, the phase line, working zero line and protective line shall be distinguished in<\/p>\n<p>different colors to prevent the phase line from being mixed with the zero line or the working zero line from being mixed with the protective zero<\/p>\n<p>line. In order to ensure the correct connection of various sockets, the three-phase five wire power distribution mode shall be used.<\/p>\n<p>(5) For the automatic air switch or fuse of the power supply at the user end, a single-phase leakage protector shall be installed in it. The user lines<\/p>\n<p>that have been out of repair for a long time, aging insulation or increased load, and the section is not small, should be replaced as soon as possible<\/p>\n<p>to eliminate electrical fire hazards and provide conditions for the normal operation of the leakage protector.<\/p>\n<p>(6) In any case, the protective grounding wire and neutral wire of the three item five wire system equipment in the power electrical system shall not<\/p>\n<p>be less than 1\/2 of the phase line, and the grounding wire and neutral wire of the lighting system, whether three item five wire or single item three<\/p>\n<p>wire system, must be the same as the item line.<\/p>\n<p>(7) The main line of working grounding and protective grounding is allowed to be shared, but its section shall not be less than half of the section<\/p>\n<p>of phase line.<\/p>\n<p>(8) The grounding of each electrical device shall be connected to the grounding main line with a separate grounding wire. It is not allowed to connect<\/p>\n<p>several electrical devices that need to be grounded in series in one grounding wire.<\/p>\n<p>(9) The section of bare copper grounding wire of 380V distribution box, maintenance power box and lighting power box shall be&gt;4 mm<sup>2<\/sup>, the section<\/p>\n<p>of bare aluminum wire shall be&gt;6 mm2, the section of insulated copper wire shall be&gt;2.5 mm2, and the section of insulated aluminum wire shall be&gt;4 mm<sup>2<\/sup>.<\/p>\n<p>(10) The distance between the grounding wire and the ground should be 250-300mm.<\/p>\n<p>(11) Working grounding shall be painted on the surface with yellow and green stripes, protective grounding shall be painted on the surface with black,<\/p>\n<p>and neutral line of equipment shall be painted with light blue mark.<\/p>\n<p>(12) It is not allowed to use the metal sheath or metal mesh of snakeskin pipe, pipe insulation layer and cable metal sheath as the grounding wire.<\/p>\n<p>(13) When the ground wire is welded, the lap welding shall be used for welding the ground wire. The lap length must meet the requirements that the flat<\/p>\n<p>steel is 2 times its width (and at least 3 edges are welded), and the round steel is 6 times its diameter (and double-sided welding is required). When the<\/p>\n<p>round steel is connected with the flat iron, the lap welding length is 6 times of the round steel (and double-sided welding is required).<\/p>\n<p>(14) Copper and aluminum wires must be crimped with fixing screws to connect with the grounding bar, and shall not be twisted. When flat copper<\/p>\n<p>flexible wires are used as grounding wires, the length shall be appropriate, and the crimping lug shall be connected with the grounding screw.<\/p>\n<p>(15) During the operation of the equipment, the operator shall check that the grounding wire of the electrical equipment is well connected with the<\/p>\n<p>grounding grid and electrical equipment, and there is no breakage that reduces the section of the grounding wire, otherwise it will be treated as a defect.<\/p>\n<p>(16) During the acceptance of equipment maintenance, it is necessary to check that the grounding wire of electrical equipment is in good condition.<\/p>\n<p>(17) The Equipment Department shall regularly check the grounding of electrical equipment, and timely notify the rectification in case of any problem.<\/p>\n<p>(18) The grounding resistance of electrical equipment shall be monitored according to the provisions of the cycle or during major and minor maintenance<\/p>\n<p>of the equipment. If problems are found, the causes shall be analyzed and handled in a timely manner.<\/p>\n<p>(19) The grounding of high-voltage electrical equipment and the grounding resistance of the grounding grid shall be conducted by the Equipment<\/p>\n<p>Department in accordance with the Code for Handover and Preventive Test of Electric Equipment, and the grounding of low-voltage electrical equipment<\/p>\n<p>shall be conducted by the department under the jurisdiction of the equipment.<\/p>\n<p>(20) The incoming short circuit current of the grounding device adopts the maximum symmetrical component of the maximum short circuit current<\/p>\n<p>flowing into the ground through the grounding device in case of internal and external short circuit of the grounding device. The current shall be determined<\/p>\n<p>according to the maximum operation mode of the system after 5 to 10 years of development, and the short circuit current distribution between the<\/p>\n<p>grounding neutral points in the system and the separated grounding short circuit current in the lightning conductor shall be considered.<\/p>\n<p>\u00a0<\/p>\n<p><strong>The following equipment must be grounded<\/strong><\/p>\n<p>(1) Secondary coil of current transformer.<\/p>\n<p>(2) Enclosures of distribution boards and control panels.<\/p>\n<p>(3) The enclosure of the motor.<\/p>\n<p>(4) The shell of the cable joint box and the metal sheath of the cable.<\/p>\n<p>(5) The metal base or housing of the switch and its transmission device.<\/p>\n<p>(6) Metal base of high-voltage insulator and bushing.<\/p>\n<p>(7) Metal pipes for indoor and outdoor wiring.<\/p>\n<p>(8) Metering meter grounding terminal.<\/p>\n<p>(9) Enclosures for electrical and lighting equipment.<\/p>\n<p>(10) Metal frame of indoor and outdoor power distribution equipment and metal barrier of live parts.<\/p>\n<p>\u00a0<\/p>\n<p><strong>Relevant requirements for motor grounding<\/strong><\/p>\n<p>(1) The motor grounding wire should be connected with the grounding grid of the whole plant by flat iron. If it is far from the grounding main<\/p>\n<p>line or the flat iron grounding wire is arranged to affect the beauty of the environment, the natural grounding body should be used as far as<\/p>\n<p>possible, or flat copper wire should be used as the grounding wire.<\/p>\n<p>(2) For motors with grounding screws on the shell, the grounding wire must be connected with the grounding screw.<\/p>\n<p>(3) For motors without grounding screws on the shell, it is required to install grounding screws at appropriate positions on the motor shell to<\/p>\n<p>connect with the grounding wire.<\/p>\n<p>(4) The motor shell with reliable electrical contact with the grounded base may not be grounded, and the grounding wire shall be arranged<\/p>\n<p>neatly and beautifully.<\/p>\n<p>\u00a0<\/p>\n<p><strong>Relevant requirements for switchboard grounding<\/strong><\/p>\n<p>(1) The grounding wire of the distribution board should be connected with the grounding grid of the whole plant by flat iron. If it is far from<\/p>\n<p>the grounding main line or the flat iron grounding wire layout affects the beauty of the environment, the natural grounding body should be<\/p>\n<p>used as far as possible, or soft copper wire should be used as the grounding wire.<\/p>\n<p>(2) When bare copper conductor is used as grounding wire of low-voltage switchboard, the section shall not be less than 6mm2, and when<\/p>\n<p>insulated copper wire is used, the section shall not be less than 4mm2.<\/p>\n<p>(3) For the distribution board with grounding screw on the shell, the grounding wire must be connected with the grounding screw.<\/p>\n<p>(4) For the distribution board without grounding screw on the shell, it is required to install grounding screw at the proper position of the<\/p>\n<p>distribution board shell to connect with the grounding phase line.<\/p>\n<p>(5) The shell of the distribution board with reliable electrical contact with the grounding body can be ungrounded.<\/p>\n<p>\u00a0<\/p>\n<p><strong>Inspection and measurement method of grounding wire<\/strong><\/p>\n<p>(1) Before the test, a sufficient safety distance shall be kept from the tested equipment to prevent accidental contact with live and rotating parts,<\/p>\n<p>and the test shall be carried out by two people.<\/p>\n<p>(2) Before the test, select the resistance gear of the multimeter, short the two probes of the multimeter, and the resistance gear of the calibration<\/p>\n<p>meter indicates 0.<\/p>\n<p>(3) Connect one end of the probe to the ground wire and the other end to the special terminal for equipment grounding.<\/p>\n<p>(4) When the tested equipment does not have a special grounding terminal, the other end of the probe shall be measured on the enclosure or<\/p>\n<p>metal component of the electrical equipment.<\/p>\n<p>(5) The main grounding grid or the reliable connection with the main grounding grid must be selected as the grounding terminal, and the<\/p>\n<p>surface oxide must be removed to ensure good contact.<\/p>\n<p>(6) The value shall be read after the meter indication is stable, and the grounding resistance value shall comply with the regulations.<\/p>\n<div><\/div>","protected":false},"excerpt":{"rendered":"<p>What are the specifications and requirements for electrical grounding ? The protection methods for electrical system configuration include: protective grounding, protective neutral connection, repeated grounding, working grounding, etc. A g<\/p>","protected":false},"author":1,"featured_media":897,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[27],"tags":[],"class_list":["post-1300","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"_links":{"self":[{"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/posts\/1300","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/comments?post=1300"}],"version-history":[{"count":0,"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/posts\/1300\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/media\/897"}],"wp:attachment":[{"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/media?parent=1300"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/categories?post=1300"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.yojiuelec.com\/hi\/wp-json\/wp\/v2\/tags?post=1300"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}